Material
|
aluminum alloy wires
|
Standard
|
BS 3242 / BS EN 50182 / IEC 61089 / ASTM B 399/B 399M / DIN 48201-6 standards
|
Application
|
AAAC conductor have been widely used in overhead transmission and substation power lines
|
Electrical Properties
|
Density at 20ºC: 2.70 kg/dm
Temperature Coefficient at 20°C: 0.00360 (°C)
Resistivity at 20°C: 0.0326 Ohms mm²/m
Linear Expansivity: 23 x10-6(°C)
|
Service Conditions
|
Ambient Temperature: -5°C - 50°C
Wind Pressure: 80 - 130kg/m²
Seismic Acceleration: 0.12 - 0.05g
Isokeraunic Level: 10 - 18
Relative Humidity: 5 - 100%
|
ALL ALUMINIUM ALLOY CONDUCTOR DIN 48201 | ||||||
Nominal area |
Actual area |
Stranding and wire diameter |
Overall diameter |
Linear mass |
Nominal Breaking Load | Max. DC resistance at 20ºC |
mm2 | mm2 | No./mm | mm | kg/km | daN | Ω/km |
16 | 15.89 | 7/1.71 | 5.1 | 43 | 444 | 2.091 |
25 | 24.25 | 7/2.10 | 6.3 | 66 | 677 | 1.3703 |
35 | 34.36 | 7/2.50 | 7.5 | 94 | 960 | 0.9669 |
50 | 49.48 | 7/3.00 | 9.0 | 135 | 1382 | 0.6714 |
50 | 48.36 | 19/1.80 | 9.0 | 133 | 1350 | 0.6905 |
70 | 65.82 | 19/2.10 | 10.5 | 181 | 1838 | 0.5073 |
95 | 93.27 | 19/2.50 | 12.5 | 256 | 2605 | 0.3579 |
120 | 117 | 19/2.80 | 14.0 | 322 | 3268 | 0.2854 |
150 | 147 | 37/2.25 | 15.2 | 406 | 4109 | 0.2274 |
185 | 181 | 37/2.5 | 17.5 | 501 | 5073 | 0.1842 |
240 | 242.54 | 61/2.25 | 20.2 | 670 | 6774 | 0.1383 |
300 | 299.43 | 61/2.50 | 22.5 | 827 | 8363 | 0.112 |
400 | 400.14 | 61/2.89 | 26.0 | 1104 | 11176 | 0.0838 |
500 | 499.83 | 61/3.23 | 29.1 | 1379 | 13960 | 0.06709 |
625 | 626.2 | 91/2.96 | 32.6 | 1732 | 17490 | 0.054 |
800 | 802.1 | 91/3.35 | 36.9 | 2218 | 22402 | 0.0418 |
1000 | 999.71 | 91/3.74 | 41.1 | 2767 | 27922 | 0.0335 |